Straight Separable Connector

Insutek AZC series of Straight Connector, is made from EPDM rubber, which consist of 3 layers: inner conductive layer, insulating layer and outer conductive layer. The Straight Connector is used in the outline of Ring Main Unit and Transformer.

Test and Standard:

  1. Rated Up to 24KV
  2. Rated current 250A
  3. AC withstand voltage 54kV/5mins, Partial discharge at 24kV ≤10pC
  4. Standard: IEC 60502.4, EN 50180
  5. Fit for bushing interface Type A

 

Feature:

  1. Fully insulated, fully sealed and fully screened
  2. Excellent stress control
  3. Easy and safe installation, No special Tool
  4. Compact design
  5. Long shelf life

 

Related products

No data

 
 

Insutek AZC series of Straight Connector, is made from EPDM rubber, which consist of 3 layers: inner conductive layer, insulating layer and outer conductive layer. The Straight Connector is used in the outline of Ring Main Unit and Transformer

 

Standard

IEC 60502

Voltage classes

6/10(12)kV

8.7/15(17.5)kV

12/20(24)kV

18/30(36)kV

Partial discharge test at ambient temperature 

10kV, <10pC

15kV, <10pC

20kV, <10pC

30kV, <10pC

AC withstand voltage test 

27kV 5min

39kV 5min

54kV 5min

81kV 5min

Impulse voltage withstand

±75kV each polarity 10 times

±95kV each polarity 10 times

±125kV each polarity 10 times

±170kV each polarity 10 times

Size & Type

Rated Voltage (KV)

Rated Current (A)

Section(mm2)

AZC2-15/250

15

250

25~300

AZC2-24/250

24

250

35~240

Cable Core Insulation Diameter Range

6.35/11(12)KV

 8.7/15(17.5)KV

12/20(24)KV

Min(mm)

Max(mm)

Cable section (mm2)

Cable section (mm2)

Cable section (mm2)

Φ16.2

Φ20.9

50~95

25~70

35~50

Φ21.7

Φ23.0

120~150

95~120

70

Φ24.1

Φ26.5

185~240

150~185

95~120

Φ27.0

Φ29.5

300

240

150~185

Φ16.2

Φ32.5

 

300

240

 

Order Information

Rated Voltage: 15KV □  24KV □

Rated Current: 250A

Cable Type & Size: 6.35/11(12)KV □  8.7/15(17.5)KV □ 12/20(24)KV □ 18/30(36)KV

Conductor Material: Copper □   Aluminum □

Conductor Cross Section Area (mm2):  25 □ 35 □ 50 □ 75 □ 90 □ 120 □ 150 □ 185 □ 240 □

Please type √,after confirm corresponding selection

 

Note:

1.For power cable with copper shield, please ensure with reliable grounding.

2.Can not be used in explosive atmosphere

3.During installation, do not damage the cable insulation