Heat Shrink Jointing Kit

Insutek HSJK Heat Shrink Jointing kit, is specially designed for XLPE or EPR insulated, 1 or 3 cores cables up to 36kV.

 

Features:

High mechanical strength

Reliable stress control

Wide cross section range suitable for different types of conductors

Compact dimensions

Excellent UV and weathering stability 

More than 10 Years of Shelf Life ((-10℃ to 40℃ and < 75% relative humidity)

Passed type test according to IEC 60502

Related products

No data

 
 

Insutek HSJK Heat Shrink Jointing kit, is specially designed for XLPE or EPR insulated, 1 or 3 cores cables up to 36kV.

Standard

IEC 60502

Voltage classes

6/10(12)kV

8.7/15(17.5)kV

12/20(24)kV

18/30(36)kV

Partial discharge test at ambient temperature 

10kV, <10pC

15kV, <10pC

20kV, <10pC

30kV, <10pC

AC withstand voltage test 

27kV 5min

39kV 5min

54kV 5min

81kV 5min

Impulse voltage withstand

±75kV each polarity 10 times

±95kV each polarity 10 times

±125kV each polarity 10 times

±170kV each polarity 10 times

6.35/11(12)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

HSJK-12/1×25-50

12.0mm-16.0mm

25mm²--50mm²

HSJK-12/1×70-150

17.6mm-22.8mm

70-mm²--150mm²

HSJK-12/1×185-300

24.0mm-31.0mm

185mm²--300mm²

HSJK-12/1×400-500

31.5mm-37.0mm

400mm²--500mm²

HSJK-12/1×630

38.0mm-41.9mm

630mm²

1x3 cores 

HSJK-12/3×25-50

12.0mm-16.0mm

25mm²--50mm²

HSJK-12/3×70-150

17.6mm-22.8mm

70-mm²--150mm²

HSJK-12/3×185-300

24.0mm-31.0mm

185mm²--300mm²

HSJK-12/3×400-500

31.5mm-37.0mm

400mm²--500mm²

 

8.7/15(17.5)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

HSJK-17.5/1×25-50

16.0mm-19.5mm

25mm²--50mm²

HSJK-17.5/1×70-150

20.3mm-23.5mm

70-mm²--150mm²

HSJK-17.5/1×185-300

24.0mm-31.0mm

185mm²--300mm²

HSJK-17.5/1×400-500

31.5mm-37.0mm

400mm²--500mm²

HSJK-17.5/1×630

38.0mm-41.9mm

630mm²

1x3 cores 

HSJK-17.5/3×25-50

16.0mm-19.5mm

25mm²--50mm²

HSJK-17.5/3×70-150

20.3mm-23.5mm

70-mm²--150mm²

HSJK-17.5/3×185-300

24.0mm-31.0mm

185mm²--300mm²

HSJK-17.5/3×400-500

31.5mm-37.0mm

400mm²--500mm²

 

12/20(24)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

HSJK-24/1×25-50

17.5mm-20.3mm

25mm²--50mm²

HSJK-24/1×70-150

21.5mm-26.5mm

70-mm²--150mm²

HSJK-24/1×185-300

27.5mm-33.0mm

185mm²--300mm²

HSJK-24/1×400-500

34.2mm-39.5mm

400mm²--500mm²

HSJK-24/1×630

40.5mm-43.0mm

630mm²

1x3 cores 

HSJK-24/3×25-50

17.5mm-20.3mm

25mm²--50mm²

HSJK-24/3×70-150

21.5mm-26.5mm

70-mm²--150mm²

HSJK-24/3×185-300

27.5mm-32.8mm

185mm²--300mm²

HSJK-24/3×400-500

33.5mm-39.5mm

400mm²--500mm²

 

18/30(36)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

HSJK-36/1×50-95

25.0mm-29.5mm

50mm²--95mm²

HSJK-36/1×120-240

30.5mm—36.5mm

120mm²--240mm²

HSJK-36/1×300-400

38.0mm-42.5mm

300mm2-400mm²

HSJK-36/1×500-630

43.5mm-48.5mm

500mm2--630mm²

1x3 cores

HSJK-36/3×50-95

25.0mm-29.5mm

50mm²--95mm²

HSJK-36/3×120-240

30.5mm—36.5mm

120mm²--240mm²

HSJK-36/3×300-400

38.0mm-42.5mm

300mm2--400mm²

 

Note:

  1. Before Ordering, please specify the cable structure, and Cable insulation outer diameter
  2. The above selection is according to the IEC Standard Cable