Cold Shrink Jointing Kit

Insutek KCSJ Cold Shrink Jointing kit, is specially designed for XLPE or EPR insulated, 1 or 3 cores cables up to 36kV.

 

Features:

High mechanical strength

Reliable stress control

Wide cross section range suitable for different types of conductors

Compact dimensions

Excellent UV and weathering stability 

More than 10 Years of Shelf Life ((-10℃ to 40℃ and < 75% relative humidity)

Passed type test according to IEC 60502

Related products

No data

 
 

Insutek KCSJ Cold Shrink Jointing kit, is specially designed for XLPE or EPR insulated, 1 or 3 cores cables up to 36kV.

Standard

IEC 60502

Voltage classes

6/10(12)kV

8.7/15(17.5)kV

12/20(24)kV

18/30(36)kV

26/35(40.5)kV

Partial discharge test at ambient temperature 

10kV, <10pC

15kV, <10pC

20kV, <10pC

30kV, <10pC

45kV, <10pC

AC withstand voltage test 

27kV 5min

39kV 5min

54kV 5min

81kV 5min

117kV 5min

Impulse voltage withstand

±75kV each polarity 10 times

±95kV each polarity 10 times

±125kV each polarity 10 times

±170kV each polarity 10 times

±200kV each polarity 10 times

6/10(12) KV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

KCSJ-12-7095-1

16.5mm—19.7mm

70mm²--95mm²

KCSJ-12-1215-1

19.7mm—23.5mm

120mm²--150mm²

KCSJ-12-1830-1

22.5mm—31.3mm

185mm²--300mm²

KCSJ-12-4063-1

28.9mm—38.0mm

400mm²--630mm²

1x3 cores 

KCSJ12-7095-3

16.5mm—19.7mm

70mm²--95mm²

KCSJ-12-1215-3

19.7mm—23.5mm

120mm²--150mm²

KCSJ-12-1830-3

22.5mm—31.3mm

185mm²--300mm²

KCSJ-12-4063-3

28.9mm—38.0mm

400mm²--630mm²

 

8.7/15(17.5)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

KCSJ-17.5-2550-1

16.5mm—19.7mm

25mm²--50mm²

KCSJ-17.5-7012-1

19.7mm—23.5mm

70mm²--120mm²

KCSJ-17.5-1530-1

22.5mm—31.3mm

150mm²--300mm²

KCSJ-17.5-4050-1

28.9mm—38.0mm

400mm²--500mm²

KCSJ-17.5-630-1

38.0m m—44.1mm

630mm²

1x3 cores 

 

KCSJ-17.5-2550-3

16.5mm—19.7mm

25mm²--50mm²

KCSJ-17.5-7012-3

19.7mm—23.5mm

70mm²--120mm²

KCSJ-17.5-1530-3

22.5mm—31.3mm

150mm²--300mm²

KCSJ-17.5-4050-3

28.9mm—38.0mm

400mm²--500mm²

KCSJ-17.5-630-3

38.0mm—44.1mm

630mm²

 

12/20(24)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

KCSJ-24-3550-1

19.7mm—23.5mm

35mm²--50mm²

KCSJ-24-7015-1

22.5mm—31.3mm

70mm²--150mm²

KCSJ-17.5-1840-1

28.9mm—38.0mm

185mm²--40mm²

KCSJ-17.5-5063-1

38.0mm—44.1mm

500mm²--630mm²

1x3 cores 

 

KCSJ-24-3550-3

19.7mm—23.5mm

35mm²--50mm²

KCSJ-24-7015-3

22.5mm—31.3mm

70mm²--150mm²

KCSJ-17.5-1840-3

28.9mm—38.0mm

185mm²--40mm²

KCSJ-17.5-5063-3

38.0mm—44.1mm

500mm²--630mm²

 

18/30(36)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

KCSJ-36-5015-1

25.9mm—33.9mm

50mm²--150mm²

KCSJ-36-1830-1

33.7mm—41.3mm

185mm²--300mm²

KCSJ-36-4050-1

41.3mm—47.0mm

400mm²--500mm²

KCSJ-36-630-1

47.0mm—53.5mm

630mm²

1x3 cores 

KCSJ-36-5015-3

25.9mm—33.9mm

50mm²--150mm²

KCSJ-36-1830-3

33.7mm—41.3mm

185mm²--300mm²

KCSJ-36-4050-3

41.3mm—47.0mm

400mm²--500mm²

KCSJ-36-630-3

47.0mm—53.5mm

630mm²

 

26/35(40.5)kV

Joint

Cable Insulation OD(mm)

Cable Conductor Cross-section(mm²)

1x1 core 

KCSJ-40.5-5015-1

33.7mm—41.6mm

50mm²--150mm²

KCSJ-40.5-1830-1

41.3mm—47.0mm

185mm²--300mm²

KCSJ-40.5-4063-1

47.0mm—53.5mm

400mm²--630mm²

1x3 cores 

KCSJ-40.5-5015-3

33.7mm—41.6mm

50mm²--150mm²

KCSJ-40.5-1830-3

41.3mm—47.0mm

185mm²--300mm²

KCSJ-40.5-4063-3

47.0mm—53.5mm

400mm²--630mm²

Note:

  1. Before Ordering, please specify the cable structure, and Cable insulation outer diameter
  2. The above selection is according to the IEC Standard Cable